      西門子PLC模塊CPU314C-2PN/DP

      簡(jiǎn)要描述:西門子PLC模塊CPU314C-2PN/DP,西門子S7-300CPU314C-2PN/DP,SIMATIC S7-300, CPU 314C-2PN/DP 緊湊型CPU帶有192 KB工作存儲(chǔ)區(qū), 24 數(shù)字量輸入/16 數(shù)字量輸出, 4模擬量輸入, 2模擬量輸出, 1 PT100, 4 快速計(jì)數(shù)器 (60 KHZ), 1. 接口 MPI/DP 12MBIT/S, 2. 接口以太網(wǎng) PROFIN

      • 產(chǎn)品型號(hào):
      • 廠商性質(zhì):代理商
      • 更新時(shí)間:2017-09-17
      • 訪  問(wèn)  量:1514

      詳細(xì)介紹

      西門子PLC模塊CPU314C-2PN/DP,西門子S7-300CPU314C-2PN/DP,西門子CPU314C-2PN/DP,CPU314C-2PN/DP,西門子S7-300CPU314C-2PN/DP可編程控制器

      訂貨號(hào):6ES7314-6EH04-0AB0

      SIMATIC S7-300, CPU 314C-2PN/DP 緊湊型CPU帶有192 KB工作存儲(chǔ)區(qū), 24 數(shù)字量輸入/16 數(shù)字量輸出, 4模擬量輸入, 2模擬量輸出, 1 PT100, 4 快速計(jì)數(shù)器 (60 KHZ), 1. 接口 MPI/DP 12MBIT/S, 2. 接口以太網(wǎng) PROFINET, 含 2個(gè) PORT SWITCH, 集成 24V DC 電源, FRONT C

      德國(guó)* 現(xiàn)貨銷售 質(zhì)保一年 歡迎詢價(jià)

      SIEMENS上海翰粵自動(dòng)化系統(tǒng)有限公司

       

      上海翰粵公司在經(jīng)營(yíng)活動(dòng)中精益求精,具備如下業(yè)務(wù)優(yōu)勢(shì):
      SIEMENS 可編程控制器
        1、 SIMATIC S7 系列PLC:S7-200、S7-1200、S7-300、S7-400、ET-200
        2、 邏輯控制模塊 LOGO!230RC、230RCO、230RCL、24RC、24RCL等
        3、 SITOP直流電源 24V DC 1.3A、2.5A、3A、5A、10A、20A、40A可并聯(lián).

      4、HMI 觸摸屏TD200 TD400C K-TP OP177 TP177,MP277 MP377,
      SIEMENS 交、直流傳動(dòng)裝置
        1、 交流變頻器 MICROMASTER系列:MM420、MM430、MM440、G110、G120.  

        MIDASTER系列:MDV
        2、全數(shù)字直流調(diào)速裝置 6RA23、6RA24、6RA28、6RA70、6SE70系列

      SIEMENS 數(shù)控 伺服

      SINUMERIK:801、802S 、802D、802D SL、810D、840D、611U、S120

      系統(tǒng)及伺報(bào)電機(jī),力矩電機(jī),直線電機(jī),伺服驅(qū)動(dòng)等備件銷售。

      西門子PLC模塊CPU314C-2PN/DP,西門子S7-300CPU314C-2PN/DP, 概述

      • 帶集成的數(shù)字量和模擬量輸入/輸出的緊湊型 CPU
      • 對(duì)二進(jìn)制和浮點(diǎn)數(shù)運(yùn)算具有較高的處理能力
      • 用于通過(guò) PROFIBUS 和 PROFINET 進(jìn)行分布式 I/O 連接。
      • 組合 MPI/PROFIBUS DP-主/從接口
      • 用于 2 端口交換機(jī)的 PROFINET 接口
      • PROFINET I/O 控制器,用于在PROFINET上運(yùn)行分布式I/O
      • PROFINET I-Device,用于連接作為智能 PROFINET 設(shè)備、帶 SIMATIC 或第三方 PROFINET I/O 控制器的 CPU
      • 在PROFINET上實(shí)現(xiàn)基于組件的自動(dòng)化(CBA)
      • PROFINET 代理,用于基于組件的自動(dòng)化(CBA)中的 PROFIBUS DP 智能設(shè)備
      • 集成 Web 服務(wù)器,帶有創(chuàng)建用戶定義的 Web 站點(diǎn)的選項(xiàng)
      • 經(jīng)由 PROFIBUS 的等時(shí)同步模式

      CPU 運(yùn)行需要 SIMATIC 微存儲(chǔ)卡(MMC)。

      ,西門子S7-300CPU314C-2PN/DP 應(yīng)用領(lǐng)域

      CPU 314C-2 DP 是緊湊型 CPU,適合安裝在分布式結(jié)構(gòu)中。通過(guò)其擴(kuò)展工作存儲(chǔ)器,該緊湊型CPU也適用于中等規(guī)模的應(yīng)用。集成的數(shù)字量和模擬量輸入和輸出可與過(guò)程信號(hào)直接連接。集成的 的PROFIBUS DP 主站/從站以及 PROFINET IO 控制器/I-設(shè)備接口,用于 PROFIBUS 和 PROFINET 的分布式連接。這使得 CPU 314C-2 PN/DP 可作為進(jìn)行快速處理的分布式單元使用,也可作為 PROFIBUS 和 PROFINET 系統(tǒng)中具有低端現(xiàn)場(chǎng)總線系統(tǒng)的上位控制器。

      集成技術(shù)工程的其他用途包括:

      • 計(jì)數(shù)
      • 頻率測(cè)量
      • 周期測(cè)量
      • 脈寬調(diào)制
      • PID 控制
      • 定位控制

      ,西門子S7-300CPU314C-2PN/DP

      CPU 314C-2 DP 安裝有:

      • 微處理器;
        每條二進(jìn)制指令執(zhí)行時(shí)間約60ns,每條浮點(diǎn)數(shù)運(yùn)行指令約0.59µs.
      • 擴(kuò)展存儲(chǔ)器;
        與執(zhí)行相關(guān)的程序段的 192 KB 高速 RAM(相當(dāng)于約 64 K 指令)可以為用戶程序提供足夠的空間;
        SIMATIC 微型存儲(chǔ)卡(zui大 8 MB)作為程序的裝載存儲(chǔ)器,還允許將項(xiàng)目(包括符號(hào)和注釋)存儲(chǔ)在 CPU 中。
      • 靈活的擴(kuò)展能力
        多達(dá) 31 個(gè)模塊,(4排結(jié)構(gòu))
      • 多點(diǎn)接口(MPI);
        集成的 MPI 接口zui多可以同時(shí)建立與 S7-300/400 或編程設(shè)備、PC、OP 的 12 條連接。在這些連接中,總要分別為 PG 和 OP 各保留一個(gè)連接。通過(guò)“全局?jǐn)?shù)據(jù)通訊”,MPI可以用來(lái)建立zui多16個(gè)CPU組成的簡(jiǎn)單網(wǎng)絡(luò)。
      • PROFIBUS DP 接口:
        帶有 PROFIBUS DP 主/從接口的 CPU 314C-2 DP 可以用來(lái)建立高速、易用的分布式自動(dòng)化系統(tǒng)。 對(duì)用戶來(lái)說(shuō),分布式I/O單元可作為一個(gè)集中式單元來(lái)處理(相同的組態(tài)、編址和編程).
      • 以太網(wǎng)接口;
        CPU 314C-2 PN/DP 的第 2 個(gè)內(nèi)置接口是一個(gè)基于以太網(wǎng) TCP/IP 的 PROFINET 接口,帶有雙端口交換機(jī)。
        它支持下列協(xié)議:
        • S7通訊用于在SIMATIC控制器間進(jìn)行數(shù)據(jù)交換;
        • 用于通過(guò) STEP 7 編程、調(diào)試和診斷的編程器/OP通訊
        • 與HMI和SCADA連接的PG/OP通訊;
        • 通過(guò) PROFINET 進(jìn)行的開放式 TCP/IP、UDP 和 ISO-on-TCP (RFC1006) 通訊
        • SIMATIC NET OPC-Server用于與其它控制器以及CPU自帶的I/O設(shè)備進(jìn)行通訊
      • 內(nèi)置輸入/輸出;
        24路數(shù)字量輸入(所有輸入都可用作中斷處理)和16路數(shù)字量輸出,以及5個(gè)模擬量輸入和2個(gè)模擬量輸出,使得CPU 314C-2 DP是一款*的控制器。

      ,西門子S7-300CPU314C-2PN/DP 設(shè)計(jì)

      • 口令保護(hù);
        用戶程序使用密碼保護(hù),可防止非法訪問(wèn)。
      • 塊加密
        相關(guān)功能 (FC) 和 功能塊 (FB) 可以加密的方式存儲(chǔ)于 CPU 以保護(hù)專門知識(shí)應(yīng)用。
      • 診斷緩沖;
        zui后500個(gè)故障和中斷事件保存在該緩沖區(qū)中,供診斷使用。 其中,保留zui后 100 個(gè)條目
      • 免維護(hù)的數(shù)據(jù)后備;
        如果發(fā)生斷電,則可通過(guò) CPU 將所有數(shù)據(jù)(zui多達(dá) 64 KB)自動(dòng)寫入到 SIMATIC 微型存儲(chǔ)卡(MMC 卡)上,且將在再次通電時(shí)保持不變。

      可參數(shù)化的特性

      可以使用 STEP 7 對(duì) S7 的組態(tài)、屬性以及CPU的響應(yīng)進(jìn)行參數(shù)設(shè)置:

      • 概要:
        定義名稱、系統(tǒng)號(hào)和位置號(hào)
      • 啟動(dòng);
        定義 CPU 的啟動(dòng)特性和監(jiān)視時(shí)間
      • 同步循環(huán)中斷;
        設(shè)置 IO 系統(tǒng)編號(hào)、過(guò)程映像分區(qū)編號(hào)和延時(shí)
      • 循環(huán)/時(shí)鐘存儲(chǔ)器;
        定義zui大的掃循環(huán)描時(shí)間和負(fù)載設(shè)置時(shí)鐘存儲(chǔ)器地址
      • 記憶性;
        定義具有保持功能的存儲(chǔ)位、計(jì)數(shù)器、定時(shí)器和數(shù)據(jù)塊的數(shù)量
      • 日時(shí)鐘中斷
        設(shè)定起始日期、起始時(shí)間和間隔周期
      • 周期中斷;
        周期設(shè)定
      • 系統(tǒng)診斷;
        定義診斷消息的處理和范圍。
      • 時(shí)鐘;
        設(shè)定 AS 內(nèi)或 MPI 上的同步方式
      • 防護(hù)等級(jí);
        說(shuō)明程序和數(shù)據(jù)訪問(wèn)授權(quán)。
      • 通訊;
        保留連接源
      • Web;
        CPU 的 Web 服務(wù)器設(shè)置
      • MPI/PROFIBUS-DP 接口:
        設(shè)置接口類型。定義節(jié)點(diǎn)地址。對(duì)操作模式進(jìn)行參數(shù)化,并組態(tài)使用 PROFIBUS DP 時(shí)的傳輸區(qū)對(duì)時(shí)間同步進(jìn)行參數(shù)化
      • PROFINET 接口;
        地址設(shè)定。對(duì) PROFINET 屬性、智能設(shè)備功能、PROFINET 上的同步類型、使用 NTP 步驟的時(shí)間同步、介質(zhì)冗余和 KeepAlive 功能進(jìn)行參數(shù)化。參數(shù)化端口 1 和端口 2
      • 數(shù)字量輸入/輸出
        地址設(shè)定,輸入繼電器和過(guò)程中斷
      • 模擬輸入/輸出
        設(shè)定地址
        輸入的情況下:設(shè)定溫度單元,測(cè)量種類,測(cè)量范圍,以及接口頻率
        輸出的情況下:設(shè)定輸出類別和輸出范圍
      • 集成功能“計(jì)數(shù)器” 
        設(shè)定地址,以及 “連續(xù)計(jì)數(shù)”“單次計(jì)數(shù)”“周期計(jì)數(shù)”“頻率測(cè)量”和“脈寬調(diào)制”模式下的參數(shù)分配
      • 集成功能“定位器” 
        設(shè)定地址,“數(shù)字輸出定位”和“模擬輸出定位”參數(shù)
      • 集成功能“規(guī)則”

      顯示功能與信息功能

      • 狀態(tài)和故障指示;
        LED 指示硬件、編程、定時(shí)或 I/O 故障以及操作狀態(tài)(如 RUN、STOP 和 Start-up)。
      • 測(cè)試功能;
        可使用編程器顯示程序執(zhí)行過(guò)程中的信號(hào)狀態(tài),可以不通過(guò)用戶程序而修改過(guò)程變量,以及輸出堆棧內(nèi)容。
      • 信息功能;
        您可以使用編程器以純文本的形式獲取 CPU 存儲(chǔ)容量和操作模式、工作存儲(chǔ)器和裝載存儲(chǔ)器的當(dāng)前利用率以及當(dāng)前循環(huán)時(shí)間和診斷緩沖區(qū)內(nèi)容的相關(guān)信息。

      集成的通訊功能

      • 編程器/OP 通訊
      • 全局?jǐn)?shù)據(jù)通訊
      • S7 基本通訊
      • S7 通訊
      • 路由
      • 數(shù)據(jù)記錄路徑
      • PROFIBUS DP 主站/從站
      • 通過(guò) TCP/IP、ISO-on-TCP 和 UDP 進(jìn)行開放式通訊
      • PROFINET IO 控制器
      • PROFINET 智能設(shè)備
      • PROFINET CBA(基于組件的自動(dòng)化)
      • Web 服務(wù)器

      集成功能

      • 計(jì)數(shù)器;
        4 個(gè)計(jì)數(shù)器(zui高 60 kHz),具有獨(dú)立方向的比較器,可直接連接到 24V 增量編碼器。
      • 4通道頻率測(cè)量;
        允許進(jìn)行頻率測(cè)量(高達(dá) 60 kHz),例如,測(cè)量軸速或吞吐量(每個(gè)測(cè)量周期內(nèi)的件數(shù))。
      • 周期測(cè)量
        用于獲取并處理計(jì)數(shù)脈沖,頻率zui高為 1 KHz
      • 脈寬調(diào)制;
        4個(gè)輸出可直接連接控制閥、執(zhí)行器、開關(guān)設(shè)備、加熱裝置等,例如采樣頻率為 2.5 kHz。 可設(shè)置周期長(zhǎng)度并可在運(yùn)行時(shí)修改占空比。
      • 定位控制
        集成在操作系統(tǒng)中的SFB可通過(guò)2路數(shù)字量輸出或1個(gè)模擬量輸出對(duì)1個(gè)軸進(jìn)行定位控制。
      • 報(bào)警輸入(所有數(shù)字量輸入);
        報(bào)警輸入可以檢測(cè)過(guò)程事件,并在zui短的時(shí)間內(nèi)觸發(fā)響應(yīng)。

      ,西門子S7-300CPU314C-2PN/DP 技術(shù)規(guī)格

       

      6ES7 314-6EH04-0AB0

      General information

       

      Hardware product version

      01

      Firmware version

      V3.3

      Supply voltage

       

      24 V DC

      Yes

      permissible range, lower limit (DC)

      19.2 V

      permissible range, upper limit (DC)

      28.8 V

      Mains buffering

       

      • Mains/voltage failure stored energy time

      5 ms

      • Repeat rate, min.

      1 s

      Digital inputs

       

      • Load voltage L+

       

        • Rated value (DC)

      24 V

        • Reverse polarity protection

      Yes

      Digital outputs

       

      • Load voltage L+

       

        • Rated value (DC)

      24 V

        • Reverse polarity protection

      No

      Input current

       

      Current consumption (rated value)

      850 mA

      Current consumption (in no-load operation), typ.

      190 mA

      Inrush current, typ.

      5 A

      I²t

      0.7 A²·s

      from supply voltage L+, max.

      850 mA

      Digital inputs

       

      • from load voltage L+ (without load), max.

      80 mA

      Digital outputs

       

      • from load voltage L+, max.

      50 mA

      Power losses

       

      Power loss, typ.

      14 W

      Memory

       

      Type of memory

      other

      Work memory

       

      • integrated

      192 kbyte

      • expandable

      No

      • Size of retentive memory for retentive data blocks

      64 kbyte

      Load memory

       

      • pluggable (MMC)

      Yes

      • pluggable (MMC), max.

      8 Mbyte

      • Data management on MMC (after last programming), min.

      10 a

      Backup

       

      • present

      Yes

      • without battery

      Yes; Program and data

      CPU processing times

       

      for bit operations, typ.

      0.06 µs

      for word operations, typ.

      0.12 µs

      for fixed point arithmetic, typ.

      0.16 µs

      for floating point arithmetic, typ.

      0.59 µs

      CPU-blocks

       

      Number of blocks (total)

      1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.

      DB

       

      • Number, max.

      1 024

      • Size, max.

      64 kbyte

      FB

       

      • Number, max.

      1 024

      • Size, max.

      64 kbyte

      FC

       

      • Number, max.

      1 024; Number range: 0 to 7999

      • Size, max.

      64 kbyte

      OB

       

      • Description

      see instruction list

      • Size, max.

      64 kbyte

      • Number of free cycle OBs

      1

      • Number of time alarm OBs

      1

      • Number of delay alarm OBs

      2

      • Number of time interrupt OBs

      4

      • Number of process alarm OBs

      1

      • Number of DPV1 alarm OBs

      3; OB 55, 56, 57

      • Number isochronous mode OBs

      1; OB 61; only for PROFINET

      • Number of startup OBs

      1

      • Number of asynchronous error OBs

      6

      • Number of synchronous error OBs

      2

      Nesting depth

       

      • per priority class

      16

      • additional within an error OB

      4

      Counters, timers and their retentivity

       

      S7 counter

       

      • Number

      256

      • Retentivity

       

        • adjustable

      Yes

        • lower limit

      0

        • upper limit

      255

        • preset

      Z 0 to Z 7

      • Counting range

       

        • adjustable

      Yes

        • lower limit

      0

        • upper limit

      999

      IEC counter

       

      • present

      Yes

      • Type

      SFB

      • Number

      Unlimited (limited only by RAM capacity)

      S7 times

       

      • Number

      256

      • Retentivity

       

        • adjustable

      Yes

        • lower limit

      0

        • upper limit

      255

        • preset

      No retentivity

      • Time range

       

        • lower limit

      10 ms

        • upper limit

      9 990 s

      IEC timer

       

      • present

      Yes

      • Type

      SFB

      • Number

      Unlimited (limited only by RAM capacity)

      Data areas and their retentivity

       

      retentive data area, total

      All, max. 64 KB

      Flag

       

      • Number, max.

      256 byte

      • Retentivity available

      Yes; MB 0 to MB 255

      • Retentivity preset

      MB 0 to MB 15

      • Number of clock memories

      8; 1 memory byte

      Data blocks

       

      • Number, max.

      1 024; Number range: 1 to 16000

      • Size, max.

      64 kbyte

      • Retentivity adjustable

      Yes; via non-retain property on DB

      • Retentivity preset

      Yes

      Local data

       

      • per priority class, max.

      32 kbyte; Max. 2048 bytes per block

      Address area

       

      I/O address area

       

      • Inputs

      2 048 byte

      • Outputs

      2 048 byte

      • of which, distributed

       

        • Inputs

      2 003 byte

        • Outputs

      2 010 byte

      Process image

       

      • Inputs

      2 048 byte

      • Outputs

      2 048 byte

      • Inputs, adjustable

      2 048 byte

      • Outputs, adjustable

      2 048 byte

      • Inputs, default

      256 byte

      • Outputs, default

      256 byte

      • Default addresses of the integrated channels

       

        • Digital inputs

      136.0 to 138.7

        • Digital outputs

      136.0 to 137.7

        • Analog inputs

      800 to 809

        • Analog outputs

      800 to 803

      Subprocess images

       

      • Number of subprocess images, max.

      1; With PROFINET IO, the length of the user data is limited to 1600 bytes

      Digital channels

       

      • Inputs

      16 048

      • Outputs

      16 096

      • Inputs, of which central

      1 016

      • Outputs, of which central

      1 008

      Analog channels

       

      • Inputs

      1 006

      • Outputs

      1 007

      • Inputs, of which central

      253

      • Outputs, of which central

      250

      Hardware configuration

       

      Expansion devices, max.

      3

      Number of DP masters

       

      • integrated

      1

      • via CP

      4

      Number of operable FMs and CPs (recommended)

       

      • FM

      8

      • CP, point-to-point

      8

      • CP, LAN

      10

      Rack

       

      • Racks, max.

      4

      • Modules per rack, max.

      8; In rack 3 max. 7

      Time of day

       

      Clock

       

      • Hardware clock (real-time clock)

      Yes

      • battery-backed and synchronizable

      Yes

      • Deviation per day, max.

      10 s; Typ.: 2 s

      • Backup time

      6 wk; At 40 °C ambient temperature

      • Behavior of the clock following POWER-ON

      Clock continues running after POWER OFF

      • Behavior of the clock following expiry of backup period

      Clock continues to run with the time at which the power failure occurred

      Operating hours counter

       

      • Number

      1

      • Number/Number range

      0

      • Range of values

      0 to 2^31 hours (when using SFC 101)

      • Granularity

      1 hour

      • retentive

      Yes; Must be restarted at each restart

      Clock synchronization

       

      • supported

      Yes

      • to MPI, master

      Yes

      • to MPI, slave

      Yes

      • to DP, master

      Yes; With DP slave only slave clock

      • to DP, slave

      Yes

      • in AS, master

      Yes

      • in AS, slave

      Yes

      • on Ethernet via NTP

      Yes; as client

      Digital inputs

       

      Number of digital inputs

      24

      • of which, inputs usable for technological functions

      16

      integrated channels (DI)

      24

      Input characteristic curve in accordance with IEC 61131, type 1

      Yes

      Number of simultaneously controllable inputs

       

      • horizontal installation

       

        • up to 40 °C, max.

      24

        • up to 60 °C, max.

      12

      • vertical installation

       

        • up to 40 °C, max.

      12

      Input voltage

       

      • Rated value, DC

      24 V

      • for signal "0"

      -3 to +5 V

      • for signal "1"

      15 to 30 V

      Input current

       

      • for signal "1", typ.

      8 mA

      Input delay (for rated value of input voltage)

       

      • for standard inputs

       

        • Parameterizable

      Yes; 0.1 / 0.3 / 3 / 15 ms (You can reconfigure the input delay of the standard inputs during program runtime. Please note that under certain circumstances your newly set filter time may not be effective until the next filter cycle.)

        • Rated value

      3 ms

      • for counter/technological functions

       

        • at "0" to "1", max.

      8 µs; Minimum pulse width/minimum pause between pulses at maximum counting frequency

      Cable length

       

      • Cable length, shielded, max.

      1 000 m

      • Cable length unshielded, max.

      600 m

      • Technological functions

       

        • shielded, max.

      50 m; at maximum count frequency

        • Unshielded, max.

      not allowed

      • Standard DI

       

        • shielded, max.

      1 000 m

        • Unshielded, max.

      600 m

      Digital outputs

       

      Number of digital outputs

      16

      • of which high-speed outputs

      4; Notice: You cannot connect the fast outputs of your CPU in parallel

      integrated channels (DO)

      16

      Short-circuit protection

      Yes; Clocked electronically

      • Response threshold, typ.

      1 A

      Limitation of inductive shutdown voltage to

      L+ (-48 V)

      Controlling a digital input

      Yes

      Switching capacity of the outputs

       

      • Lamp load, max.

      5 W

      Load resistance range

       

      • lower limit

      48 Ω

      • upper limit

      4 kΩ

      Output voltage

       

      • for signal "1", min.

      L+ (-0.8 V)

      Output current

       

      • for signal "1" rated value

      500 mA

      • for signal "1" permissible range, min.

      5 mA

      • for signal "1" permissible range, max.

      0.6 A

      • for signal "1" minimum load current

      5 mA

      • for signal "0" residual current, max.

      0.5 mA

      Parallel switching of 2 outputs

       

      • for increased power

      No

      • for redundant control of a load

      Yes

      Switching frequency

       

      • with resistive load, max.

      100 Hz

      • with inductive load, max.

      0.5 Hz

      • on lamp load, max.

      100 Hz

      • of the pulse outputs, with resistive load, max.

      2.5 kHz

      Aggregate current of outputs (per group)

       

      • horizontal installation

       

        • up to 40 °C, max.

      3 A

        • up to 60 °C, max.

      2 A

      • vertical installation

       

        • up to 40 °C, max.

      2 A

      Cable length

       

      • Cable length, shielded, max.

      1 000 m

      • Cable length unshielded, max.

      600 m

      Analog inputs

       

      Number of analog inputs

      5

      Integrated channels (AI)

      5; 4 x current/voltage, 1 x resistance

      Number of analog inputs for voltage/current measurement

      4

      Number of analog inputs for resistance/resistance thermometer measurement

      1

      permissible input frequency for current input (destruction limit), max.

      5 V

      permissible input voltage for voltage input (destruction limit), max.

      30 V; Permanent

      permissible input current for voltage input (destruction limit), max.

      0.5 mA

      permissible input current for current input (destruction limit), max.

      50 mA; Permanent

      Technical unit for temperature measurement adjustable

      Yes; Degrees Celsius / degrees Fahrenheit / Kelvin

      Input ranges

       

      • Voltage

      Yes; ±10 V / 100 kΩ; 0 V to 10 V / 100 kΩ

      • Current

      Yes; ±20 mA / 100 Ω; 0 mA to 20 mA / 100 Ω; 4 mA to 20 mA / 100 Ω

      • Resistance thermometer

      Yes; Pt 100 / 10 MΩ

      • Resistance

      Yes; 0 Ω to 600 Ω / 10 MΩ

      Input ranges (rated values), voltages

       

      • 0 to +10 V

      Yes

      • Input resistance (0 to 10 V)

      100 kΩ

      Input ranges (rated values), currents

       

      • 0 to 20 mA

      Yes

      • Input resistance (0 to 20 mA)

      100 Ω

      • -20 to +20 mA

      Yes

      • Input resistance (-20 to +20 mA)

      100 Ω

      • 4 to 20 mA

      Yes

      • Input resistance (4 to 20 mA)

      100 Ω

      Input ranges (rated values), resistance thermometers

       

      • Pt 100

      Yes

      • Input resistance (Pt 100)

      10 MΩ

      Input ranges (rated values), resistors

       

      • No-Load voltage, typ.

      3.3 V

      • Measured current, typ.

      1,25 mA

      • 0 to 600 ohms

      Yes

      • Input resistance (0 to 600 ohms)

      10 MΩ

      Thermocouple (TC)

       

      • Temperature compensation

       

        • Parameterizable

      No

      Characteristic linearization

       

      • Parameterizable

      Yes; by software

        • for resistance thermometer

      Pt 100

      Cable length

       

      • Cable length, shielded, max.

      100 m

      Analog outputs

       

      Number of analog outputs

      2

      Integrated channels (AO)

      2

      Voltage output, short-circuit protection

      Yes

      Voltage output, short-circuit current, max.

      55 mA

      Current output, no-load voltage, max.

      14 V

      Output ranges, voltage

       

      • 0 to 10 V

      Yes

      • -10 to +10 V

      Yes

      Output ranges, current

       

      • 0 to 20 mA

      Yes

      • -20 to +20 mA

      Yes

      • 4 to 20 mA

      Yes

      Connection of actuators

       

      • for voltage output two-wire connection

      Yes; Without compensation of the line resistances

      • for voltage output four-wire connection

      No

      • for current output two-wire connection

      Yes

      Load impedance (in rated range of output)

       

      • with voltage outputs, min.

      1 kΩ

      • with voltage outputs, capacitive load, max.

      0.1 µF

      • with current outputs, max.

      300 Ω

      • with current outputs, inductive load, max.

      0.1 mH

      Destruction limits against externally applied voltages and currents

       

      • Voltages at the outputs towards MANA

      16 V; Permanent

      • Current, max.

      50 mA; Permanent

      Cable length

       

      • Cable length, shielded, max.

      200 m

      Analog value creation

       

      Measurement principle

      Actual value encryption (successive approximation)

      Integrations and conversion time/resolution per channel

       

      • Resolution with overrange (bit including sign), max.

      12 bit

      • Integration time, parameterizable

      Yes; 16.6 / 20 ms

      • permissible input frequency, max.

      400 Hz

      • Interference voltage suppression for interference frequency f1 in Hz

      60 / 50 Hz

      • Conversion time (per channel)

      1 ms

      • Time constant of the input filter

      0.38 ms

      • Basic execution time of the module (all channels released)

      1 ms

      Settling time

       

      • for resistive load

      0.6 ms

      • for capacitive load

      1 ms

      • for inductive load

      0.5 ms

      Encoder

       

      Connection of signal encoders

       

      • for voltage measurement

      Yes

      • for current measurement as 2-wire transducer

      Yes; with external supply

      • for current measurement as 4-wire transducer

      Yes

      • for resistance measurement with two-wire connection

      Yes; Without compensation of the line resistances

      • for resistance measurement with three-wire connection

      No

      • for resistance measurement with four-wire connection

      No

      Connectable encoders

       

      • 2-wire sensor

      Yes

        • Permissible quiescent current (2-wire sensor), max.

      1.5 mA

      Errors/accuracies

       

      Temperature error (relative to input range), (+/-)

      0.006 %/K

      Crosstalk between the inputs, min.

      60 dB

      Repeat accuracy in steady state at 25 °C (relative to input area), (+/-)

      0.06 %

      Output ripple (based on output area, bandwidth 0 to 50 kHz), (+/-)

      0.1 %

      Linearity error (relative to output range), (+/-)

      0.15 %

      Temperature error (relative to output range), (+/-)

      0.01 %/K

      Crosstalk between the outputs, min.

      60 dB

      Repeat accuracy in steady state at 25 °C (relative to output area), (+/-)

      0.06 %

      Operational limit in overall temperature range

       

      • Voltage, relative to input area, (+/-)

      1 %

      • Current, relative to input area, (+/-)

      1 %

      • Resistance, relative to input area, (+/-)

      1 %

      • Voltage, relative to output area, (+/-)

      1 %

      • Current, relative to output area, (+/-)

      1 %

      Basic error limit (operational limit at 25 °C)

       

      • Voltage, relative to input area, (+/-)

      0.8 %; Linearity error +/- 0.06 %

      • Current, relative to input area, (+/-)

      0.8 %; Linearity error +/- 0.06 %

      • Resistance, relative to input area, (+/-)

      0.8 %; Linearity error +/- 0.2%

      • Resistance thermometer, relative to input area, (+/-)

      0.8 %

      • Voltage, relative to output area, (+/-)

      0.8 %

      • Current, relative to output area, (+/-)

      0.8 %

      Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

       

      • Series mode interference (peak value of interference < rated value of input range), min.

      30 dB

      • Common mode interference, min.

      40 dB

      Interfaces

       

      Number of USB interfaces

      0

      Number of parallel interfaces

      0

      Number of 20 mA interfaces (TTY)

      0

      Number of RS 232 interfaces

      0

      Number of RS 422 interfaces

      0

      Number of other interfaces

      1; Ethernet, 2-port switch, 2*RJ45

      1st interface

       

      Interface type

      Integrated RS 485 interface

      Physics

      RS 485

      Isolated

      Yes

      Power supply to interface (15 to 30 V DC), max.

      200 mA

      Functionality

       

      • MPI

      Yes

      • DP master

      Yes

      • DP slave

      Yes

      • Point-to-point connection

      No

      MPI

       

      • Transmission rate, max.

      12 Mbit/s

      • Services

       

        • PG/OP communication

      Yes

        • Routing

      Yes

        • Global data communication

      Yes

        • S7 basic communication

      Yes

        • S7 communication

      Yes

        • S7 communication, as client

      No; but via CP and loadable FB

        • S7 communication, as server

      Yes

      DP master

       

      • Transmission rate, max.

      12 Mbit/s

      • Number of DP slaves, max.

      124

      • Services

       

        • PG/OP communication

      Yes

        • Routing

      Yes

        • Global data communication

      No

        • S7 basic communication

      Yes; I blocks only

        • S7 communication

      Yes

        • S7 communication, as client

      No

        • S7 communication, as server

      Yes

        • Equidistance mode support

      Yes

        • Isochronous mode

      No

        • SYNC/FREEZE

      Yes

        • Activation/deactivation of DP slaves

      Yes

        • Number of DP slaves that can be simultaneously activated/deactivated, max.

      8

        • Direct data exchange (slave-to-slave communication)

      Yes; As subscriber

        • DPV1

      Yes

      • Address area

       

        • Inputs, max.

      2 kbyte

        • Outputs, max.

      2 kbyte

      • User data per DP slave

       

        • Inputs, max.

      244 byte

        • Outputs, max.

      244 byte

      DP slave

       

      • Transmission rate, max.

      12 Mbit/s

      • Automatic baud rate search

      Yes; only with passive interface

      • Address area, max.

      32

      • User data per address area, max.

      32 byte

      • Services

       

        • PG/OP communication

      Yes

        • Routing

      Yes; Only with active interface

        • Global data communication

      No

        • S7 basic communication

      No

        • S7 communication

      Yes

        • S7 communication, as client

      No

        • S7 communication, as server

      Yes; Connection configured on one side only

        • Direct data exchange (slave-to-slave communication)

      Yes

        • DPV1

      No

      • Transfer memory

       

        • Inputs

      244 byte

        • Outputs

      244 byte

      2nd interface

       

      Interface type

      PROFINET

      Physics

      Ethernet RJ45

      Isolated

      Yes

      Integrated switch

      Yes

      Number of ports

      2

      Automatic detection of transmission speed

      Yes; 10/100 Mbit/s

      Autonegotiation

      Yes

      Autocrossing

      Yes

      Change of IP address at runtime, supported

      Yes

      Media redundancy

       

      • supported

      Yes

      • Switchover time on line break, typically

      200 ms; PROFINET MRP

      • Number of stations in the ring, max.

      50

      Functionality

       

      • MPI

      No

      • DP master

      No

      • DP slave

      No

      • PROFINET IO Controller

      Yes; Also simultaneously with IO-Device functionality

      • PROFINET IO Device

      Yes; Also simultaneously with IO Controller functionality

      • PROFINET CBA

      Yes

      • Open IE communication

      Yes; Via TCP/IP, ISO on TCP, and UDP

      • Web server

      Yes

        • Number of HTTP clients

      5

      PROFINET IO Controller

       

      • Transmission rate, max.

      100 Mbit/s

      • Number of connectable IO devices, max.

      128

      • Max. number of connectable IO devices for RT

      128

        • of which in line, max.

      128

      • Number of IO devices with IRT and the option "high flexibility"

      128

        • of which in line, max.

      61

      • Number of IO Devices with IRT and the option "high performance", max.

      64

        • of which in line, max.

      64

      • IRT, supported

      Yes

      • Shared device, supported

      Yes

      • Prioritized startup supported

      Yes

        • Number of IO Devices, max.

      32

      • Activation/deactivation of IO Devices

      Yes

        • Maximum number of IO devices that can be activated/deactivated at the same time.

      8

      • IO Devices changing during operation (partner ports), supported

      Yes

        • Max. number of IO devices per tool

      8

      • Device replacement without swap medium

      Yes

      • Send cycles

      250 μs, 500 μs,1 ms; 2 ms, 4 ms (not in the case of IRT with "high flexibility" option)

      • Updating time

      250 µs to 512 ms (depending on the operating mode, see Manual "S7-300 CPU 31xC and CPU 31x, Technical Data" for more details)

      • Services

       

        • PG/OP communication

      Yes

        • Routing

      Yes

        • S7 communication

      Yes; With loadable FBs, max. configurable connections: 10, max. number of instances: 32

        • Isochronous mode

      Yes; OB 61

        • Open IE communication

      Yes; Via TCP/IP, ISO on TCP, and UDP

      • Address area

       

        • Inputs, max.

      2 kbyte

        • Outputs, max.

      2 kbyte

        • User data consistency, max.

      1 024 byte

      PROFINET IO Device

       

      • Services

       

        • PG/OP communication

      Yes

        • Routing

      Yes

        • S7 communication

      Yes; With loadable FBs, max. configurable connections: 10, max. number of instances: 32

        • Isochronous mode

      No

        • Open IE communication

      Yes; Via TCP/IP, ISO on TCP, and UDP

        • IRT

      Yes

        • PROFIenergy, supported

      Yes; With SFB 73 / 74 prepared for loadable PROFIenergy standard FB for I-Device

        • Shared device

      Yes

        • Number of IO controllers with shared device, max.

      2

      • Transfer memory

       

        • Inputs, max.

      1 440 byte; Per IO Controller with shared device

        • Outputs, max.

      1 440 byte; Per IO Controller with shared device

      • Submodules

       

        • Number, max.

      64

        • User data per submodule, max.

      1 024 byte

      PROFINET CBA

       

      • acyclic transmission

      Yes

      • Cyclic transmission

      Yes

      Open IE communication

       

      • Open IE communication, supported

      Yes

      • Number of connections, max.

      8

      • Local port numbers used at the system end

      0, 20, 21, 23, 25, 80, 102, 135, 161, 443, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535

      • Keep-alive function, supported

      Yes

      Isochronous mode

       

      Isochronous operation (application synchronized up to terminal)

      Yes; For PROFINET only

      Communication functions

       

      PG/OP communication

      Yes

      Data record routing

      Yes

      Global data communication

       

      • supported

      Yes

      • Number of GD loops, max.

      8

      • Number of GD packets, max.

      8

      • Number of GD packets, transmitter, max.

      8

      • Number of GD packets, receiver, max.

      8

      • Size of GD packets, max.

      22 byte

      • Size of GD packet (of which consistent), max.

      22 byte

      S7 basic communication

       

      • supported

      Yes

      • User data per job, max.

      76 byte

      • User data per job (of which consistent), max.

      76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)

      S7 communication

       

      • supported

      Yes

      • as server

      Yes

      • As client

      Yes

      • User data per job, max.

      See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication)

      S5-compatible communication

       

      • supported

      Yes; via CP and loadable FC

      Open IE communication

       

      • TCP/IP

      Yes; via integrated PROFINET interface and loadable FBs

        • Number of connections, max.

      8

        • Data length for connection type 01H, max.

      1 460 byte

        • Data length for connection type 11H, max.

      32 768 byte

        • Several passive connections per port, supported

      Yes

      • ISO-on-TCP (RFC1006)

      Yes; via integrated PROFINET interface and loadable FBs

        • Number of connections, max.

      8

        • Data length, max.

      32 768 byte

      • UDP

      Yes; via integrated PROFINET interface and loadable FBs

        • Number of connections, max.

      8

        • Data length, max.

      1 472 byte

      Web server

       

      • supported

      Yes

      • Number of HTTP clients

      5

      • User-defined websites

      Yes

      PROFINET CBA (at set setpoint communication load)

       

      • Setpoint for the CPU communication load

      50 %

      • Number of remote interconnection partners

      32

      • Number of functions, master/slave

      30

      • Total of all Master/Slave connections

      1 000

      • Data length of all incoming connections master/slave, max.

      4 000 byte

      • Data length of all outgoing connections master/slave, max.

      4 000 byte

      • Number of device-internal and PROFIBUS interconnections

      500

      • Data length of device-internal und PROFIBUS interconnections, max.

      4 000 byte

      • Data length per connection, max.

      1 400 byte

      • Remote interconnections with acyclic transmission

       

        • Sampling frequency: Sampling time, min.

      500 ms

        • Number of incoming interconnections

      100

        • Number of outgoing interconnections

      100

        • Data length of all incoming interconnections, max.

      2 000 byte

        • Data length of all outgoing interconnections, max.

      2 000 byte

        • Data length per connection, max.

      1 400 byte

      • Remote interconnections with cyclic transmission

       

        • Transmission frequency: Transmission interval, min.

      10 ms

        • Number of incoming interconnections

      200

        • Number of outgoing interconnections

      200

        • Data length of all incoming interconnections, max.

      2 000 byte

        • Data length of all outgoing interconnections, max.

      2 000 byte

        • Data length per connection, max.

      450 byte

      • HMI variables via PROFINET (acyclic)

       

        • Number of stations that can log on for HMI variables (PN OPC/iMap)

      3; 2x PN OPC/1x iMap

        • HMI variable updating

      500 ms

        • Number of HMI variables

      200

        • Data length of all HMI variables, max.

      2 000 byte

      • PROFIBUS proxy functionality

       

        • supported

      Yes

        • Number of linked PROFIBUS devices

      16

        • Data length per connection, max.

      240 byte; Slave-dependent

      Number of connections

       

      • overall

      12

      • usable for PG communication

      11

        • reserved for PG communication

      1

        • Adjustable for PG communication, min.

      1

        • Adjustable for PG communication, max.

      11

      • usable for OP communication

      11

        • reserved for OP communication

      1

        • adjustable for OP communication, min.

      1

        • adjustable for OP communication, max.

      11

      • usable for S7 basic communication

      8

        • Reserved for S7 basic communication

      0

        • adjustable for S7 basic communication, min.

      0

        • adjustable for S7 basic communication, max.

      8

      • usable for S7 communication

      10

        • reserved for S7 communication

      0

        • Adjustable for S7 communication, min.

      0

        • Adjustable for S7 communication, max.

      10

      • Max. total number of instances

      32

      • usable for routing

      X1 as MPI: max. 10; X1 as DP master: max. 24; X1 as DP slave (active): max. 14; X2 as PROFINET: 24 max.

      S7 message functions

       

      Number of login stations for message functions, max.

      12; Depending on the configured connections for PG/OP and S7 basic communication

      Process diagnostic messages

      Yes

      simultaneously active Alarm-S blocks, max.

      300

      Test commissioning functions

       

      Status block

      Yes; Up to 2 simultaneously

      Single step

      Yes

      Number of breakpoints

      4

      Status/control

       

      • Status/control variable

      Yes

      • Variables

      Inputs, outputs, memory bits, DB, times, counters

      • Number of variables, max.

      30

      • of which status variables, max.

      30

      • of which control variables, max.

      14

      Forcing

       

      • Forcing

      Yes

      • Force, variables

      Inputs, outputs

      • Number of variables, max.

      10

      Diagnostic buffer

       

      • present

      Yes

      • Number of entries, max.

      500

        • adjustable

      No

        • Of which powerfail-proof

      100; Only the last 100 entries are retained

      • Number of entries readable in RUN, max.

      499

        • adjustable

      Yes; From 10 to 499

        • preset

      10

      Service data

       

      • Can be read out

      Yes

      Interrupts/diagnostics/status information

       

      Diagnostics indication LED

       

      • Status indicator digital output (green)

      Yes

      • Status indicator digital input (green)

      Yes

      Integrated Functions

       

      Number of counters

      4; See "Technological Functions" manual

      Counter frequency (counter) max.

      60 kHz

      Frequency measurement

      Yes

      Number of frequency meters

      4; up to 60 kHz (see "Technological Functions" manual)

      controlled positioning

      Yes

      Integrated function blocks (closed-loop control)

      Yes; PID controller (see "Technological Functions" manual)

      PID controller

      Yes

      Number of pulse outputs

      4; Pulse width modulation up to 2.5 kHz (see "Technological Functions" Manual)

      Limit frequency (pulse)

      2.5 kHz

      Galvanic isolation

       

      Galvanic isolation digital inputs

       

      • Galvanic isolation digital inputs

      Yes

      • between the channels

      No

      • between the channels and the backplane bus

      Yes

      Galvanic isolation digital outputs

       

      • Galvanic isolation digital outputs

      Yes

      • between the channels

      Yes

      • between the channels, in groups of

      8

      • between the channels and the backplane bus

      Yes

      Galvanic isolation analog inputs

       

      • Galvanic isolation analog inputs

      Yes

      • between the channels

      No

      • between the channels and the backplane bus

      Yes

      Galvanic isolation analog outputs

       

      • Galvanic isolation analog outputs

      Yes

      • between the channels

      No

      • between the channels and the backplane bus

      Yes

      Permissible potential difference

       

      between inputs and MANA (UCM)

      8 V DC

      between MANA and M internally (UISO)

      75 VDC / 60 VAC

      Ambient conditions

       

      Operating temperature

       

      • Min.

      0 °C

      • max.

      60 °C

      Configuration

       

      Configuration software

       

      • STEP 7

      Yes; V5.5 or higher

      programming

       

      • Command set

      see instruction list

      • Nesting levels

      8

      • System functions (SFC)

      see instruction list

      • System function blocks (SFB)

      see instruction list

      • Programming language

       

        • LAD

      Yes

        • FBD

      Yes

        • STL

      Yes

        • SCL

      Yes

        • CFC

      Yes

        • GRAPH

      Yes

        • HiGraph®

      Yes

      Know-how protection

       

      • User program protection/password protection

      Yes

      • Block encryption

      Yes; With S7 block Privacy

      Dimensions

       

      Width

      120 mm

      Height

      125 mm

      Depth

      130 mm

      Weights

       

      Weight, approx.

      730 g

       

      產(chǎn)品咨詢

      留言框

      • 產(chǎn)品:

      • 您的單位:

      • 您的姓名:

      • 聯(lián)系電話:

      • 常用郵箱:

      • 省份:

      • 詳細(xì)地址:

      • 補(bǔ)充說(shuō)明:

      • 驗(yàn)證碼:

        請(qǐng)輸入計(jì)算結(jié)果(填寫阿拉伯?dāng)?shù)字),如:三加四=7

      聯(lián)系我們

      上海翰粵自動(dòng)化系統(tǒng)有限公司 公司地址:上海市松江區(qū)思賢路2399弄137號(hào)   技術(shù)支持:化工儀器網(wǎng)
      • 聯(lián)系人:黃政武
      • QQ:76868608
      • 公司傳真:021-57657276
      • 郵箱:76868608@qq.com

      掃一掃 更多精彩

      微信二維碼

      網(wǎng)站二維碼

      亚洲人成电影在线观看青青| 91亚洲国产成人久久精品网址| 亚洲国产综合专区电影在线| 伊人久久精品亚洲午夜| 亚洲成AV人影片在线观看| 亚洲综合无码无在线观看| 国产成人精品日本亚洲网址| 91亚洲国产成人精品下载| 亚洲国产综合专区电影在线 | 久久久久国产成人精品亚洲午夜| 国产精品久久久久久亚洲小说| 亚洲国产成人久久精品软件| 亚洲国产精品嫩草影院| 亚洲精品无AMM毛片| 亚洲综合欧美色五月俺也去| 亚洲中文字幕乱码AV波多JI| 亚洲精品无码日韩国产不卡av| 亚洲中文字幕无码mv| 亚洲欧好州第一的日产suv| 亚洲精品乱码久久久久久蜜桃图片 | 久久久久亚洲Av无码专| 久久精品国产亚洲AV嫖农村妇女 | 噜噜噜亚洲色成人网站| 国产成人人综合亚洲欧美丁香花| 国产精品亚洲lv粉色| 国产91成人精品亚洲精品| 亚洲人成国产精品无码| 国产精品亚洲视频| 亚洲午夜国产精品无码 | 亚洲无人区码一二三码区别图片| 亚洲AV无码专区国产乱码不卡| 久久精品国产亚洲av瑜伽| 亚洲精品网站在线观看不卡无广告| 亚洲免费一区二区| 亚洲精品中文字幕乱码三区| 久久亚洲精品中文字幕无码| 亚洲福利视频一区二区三区| 亚洲一区二区三区四区视频 | 在线综合亚洲欧洲综合网站| 亚洲精华液一二三产区| 亚洲AV中文无码乱人伦在线视色|